<section title="10.5. Cable Labelling and Registration"><subsection title="Objective"><paragraph
    title="10.5.1."


><![CDATA[<p>To facilitate cable management, and identify unauthorised additions or tampering.</p>]]></paragraph>
 </subsection>
<subsection title="Context"> <block title="Scope"><paragraph
    title="10.5.2."


><![CDATA[<p>This section covers information relating to the labelling of cabling infrastructure installed in secure areas.</p>]]></paragraph>
</block>
<block title="Applicability of controls within this section"><paragraph
    title="10.5.3."


><![CDATA[<p>The controls within this section are applicable only to communications infrastructure located within facilities in New Zealand. For deployable platforms or facilities outside New Zealand, Emanation Security Threat Assessments (<a title="Emanation Security Threat Assessment" href="http://nzism.gcsb.govt.nz/ism-document#Section-13859">Section 10.7</a>) of this chapter of this manual MUST be consulted.</p>]]></paragraph>
</block>
</subsection>
<subsection title="Rationale &amp; Controls"> <block title="Conduit label specifications"><paragraph
    title="10.5.4.R.01."

    tags="Infrastructure,Technical"


><![CDATA[<p>Conduit labelling of a specific size and colour will facilitate identifying secure conduits.</p>]]></paragraph>
<paragraph
    title="10.5.4.C.01."

    tags="Infrastructure,Technical"


    classification="All Classifications"
    compliance="Must"
    cid="2387"
><![CDATA[<p>Agencies MUST comply with the conduit label colours specified in the following table.</p><table class="table-secondary">
<tbody>
<tr>
<td>Classification</td>
<td>
<p>Cable colour</p>
</td>
</tr>
<tr>
<td>
<p>Compartmented Information (SCI)</p>
</td>
<td class="table-cell-orange">
<p>Orange/Yellow/Teal or other colour</p>
</td>
</tr>
<tr>
<td>
<p>TOP SECRET</p>
</td>
<td class="table-cell-red">Red</td>
</tr>
<tr>
<td>
<p>SECRET</p>
</td>
<td class="table-cell-blue">Blue</td>
</tr>
<tr>
<td>CONFIDENTIAL</td>
<td class="table-cell-green">Green</td>
</tr>
<tr>
<td>
<p>RESTRICTED and all lower classifications</p>
</td>
<td class="table-cell-black">Black</td>
</tr>
</tbody>
</table>]]></paragraph>
</block>
<block title="Installing conduit labelling"><paragraph
    title="10.5.5.R.01."

    tags="Infrastructure,Technical"


><![CDATA[<p>Conduit labelling in public or reception areas should not draw undue attention to the level of classified processing or any other agency capability.</p>]]></paragraph>
<paragraph
    title="10.5.5.C.01."

    tags="Infrastructure,Technical"


    classification="All Classifications"
    compliance="Should Not"
    cid="2390"
><![CDATA[<p>Conduit labels installed in public or visitor areas SHOULD NOT be labelled in such a way as to draw attention to or reveal classification of data processed or other agency capability.</p>]]></paragraph>
</block>
<block title="Labelling wall outlet boxes"><paragraph
    title="10.5.6.R.01."

    tags="Infrastructure,Technical"


><![CDATA[<p>Clear labelling of wall outlet boxes reduces the possibility of incorrectly attaching IT equipment of a lesser classification to the wrong outlet.</p>]]></paragraph>
<paragraph
    title="10.5.6.C.01."

    tags="Infrastructure,Technical"


    classification="Secret, Confidential, Top Secret"
    compliance="Must"
    cid="2393"
><![CDATA[<p>Wall outlet boxes MUST denote the classification, cable and outlet numbers.</p>]]></paragraph>
<paragraph
    title="10.5.6.C.02."

    tags="Infrastructure,Technical"


    classification="All Classifications"
    compliance="Should"
    cid="2394"
><![CDATA[<p>Wall outlet boxes SHOULD denote the classification, cable and outlet numbers.</p>]]></paragraph>
</block>
<block title="Standard operating procedures"><paragraph
    title="10.5.7.R.01."

    tags="Infrastructure,Technical,SOPs"


><![CDATA[<p>Recording labelling conventions in SOPs facilitates maintenance and fault finding.</p>]]></paragraph>
<paragraph
    title="10.5.7.C.01."

    tags="Infrastructure,Technical,SOPs"


    classification="All Classifications"
    compliance="Should"
    cid="2397"
><![CDATA[<p>The SOPs SHOULD record the site conventions for labelling and registration.</p>]]></paragraph>
</block>
<block title="Labelling cables"><paragraph
    title="10.5.8.R.01."

    tags="Infrastructure,Technical"


><![CDATA[<p>Labelling cables with the correct socket number, equipment type, source or destination minimises the likelihood of improperly cross connecting equipment and can assist in fault finding and configuration management.</p>]]></paragraph>
<paragraph
    title="10.5.8.C.01."

    tags="Infrastructure,Technical"


    classification="Top Secret, Confidential, Secret"
    compliance="Must"
    cid="2400"
><![CDATA[<p>Agencies MUST label cables at each end, with sufficient information to enable the physical identification and inspection of the cable.</p>]]></paragraph>
<paragraph
    title="10.5.8.C.02."

    tags="Infrastructure,Technical"


    classification="All Classifications"
    compliance="Should"
    cid="2401"
><![CDATA[<p>Agencies SHOULD label cables at each end, with sufficient information to enable the physical identification and inspection of the cable.</p>]]></paragraph>
</block>
<block title="Cable register"><paragraph
    title="10.5.9.R.01."

    tags="Infrastructure,Technical"


><![CDATA[<p>Cable registers provide a source of information that assessors can view to verify compliance.</p>]]></paragraph>
<paragraph
    title="10.5.9.C.01."

    tags="Infrastructure,Technical"


    classification="Top Secret, Confidential, Secret"
    compliance="Must"
    cid="2404"
><![CDATA[<p>Agencies MUST maintain a register of cables.</p>]]></paragraph>
<paragraph
    title="10.5.9.C.02."

    tags="Infrastructure,Technical"


    classification="All Classifications"
    compliance="Should"
    cid="2405"
><![CDATA[<p>Agencies SHOULD maintain a register of cables.</p>]]></paragraph>
</block>
<block title="Cable register contents"><paragraph
    title="10.5.10.R.01."

    tags="Infrastructure,Technical"


><![CDATA[<p>Cable registers allow installers and assessors to trace cabling for inspection, tampering or accidental damage. It tracks all cable management changes through the life of the system.</p>]]></paragraph>
<paragraph
    title="10.5.10.C.01."

    tags="Infrastructure,Technical"


    classification="Secret, Confidential, Top Secret"
    compliance="Must"
    cid="2408"
><![CDATA[<p>The cable register MUST record at least the following information:</p><ul>
<li>cable identification number;</li>
<li>classification;</li>
<li>socket number, equipment type, source or destination site/floor plan diagram; and</li>
<li>seal numbers if applicable.</li>
</ul>]]></paragraph>
<paragraph
    title="10.5.10.C.02."

    tags="Infrastructure,Technical"


    classification="All Classifications"
    compliance="Should"
    cid="2409"
><![CDATA[<p>The cable register SHOULD record at least the following information:</p><ul>
<li>cable identification number;</li>
<li>classification;</li>
<li>socket number, equipment type, source or destination site/floor plan diagram; and</li>
<li>seal numbers if applicable.</li>
</ul>]]></paragraph>
</block>
<block title="Cable inspections"><paragraph
    title="10.5.11.R.01."

    tags="Infrastructure,Technical"


><![CDATA[<p>Regular cable inspections, are a method of checking the cable management system against the cable register as well as detecting tampering, damage, breakages or other anomalies.</p>]]></paragraph>
<paragraph
    title="10.5.11.C.01."

    tags="Infrastructure,Technical"


    classification="All Classifications"
    compliance="Should"
    cid="2412"
><![CDATA[<p>Agencies SHOULD inspect cables for inconsistencies with the cable register in accordance with the frequency defined in the SSP.</p>]]></paragraph>
</block>
</subsection>
</section>